CVE-2017-14471

Critical

Description

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Codes: 0023, 002e, and 0037 Fault Type: Recoverable Description: The STI, EII, and HSC function files contain bits signifying whether or not a fault has occurred. Additionally there is a bit signaling the module to auto start. When these bits are set for any of the three modules and the device is moved into a run state, a fault is triggered.

SeverityCritical
CVSS10.0
Exploit probability—
ProductRockwellautomation Micrologix 1400 B Firmware
PublishedApr 5, 2018
First seenApr 5, 2018

How to fix

Sources list no fixed version or patch link for this vulnerability.

Affected products

ProductAffected versionsFixed in
rockwellautomation micrologix_1400_b_firmwarev ≤ 21.2—

Check your version

Choose the product and enter the version you run to see whether it falls in the affected range.

In the Intelligence 360 plan

Attack Surface Management

See the assets tied to your domains, the technologies they run and known vulnerabilities in one list.