CVE-2019-10929
Description
A vulnerability has been identified in SIMATIC CP 1626 (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V20.8), SIMATIC HMI Panel (incl. SIPLUS variants) (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.8.1), SIMATIC S7-1500 Software Controller (All versions < V20.8), SIMATIC S7-PLCSIM Advanced (All versions < V3.0), SIMATIC STEP 7 (TIA Portal) (All versions < V16), SIMATIC WinCC (TIA Portal) (All versions < V16), SIMATIC WinCC OA (All versions < V3.16 P013), SIMATIC WinCC Runtime Advanced (All versions < V16), SIMATIC WinCC Runtime Professional (All versions < V16), TIM 1531 IRC (incl. SIPLUS NET variants) (All versions < V2.1). Affected devices contain a message protection bypass vulnerability due to certain properties in the calculation used for integrity protection. This could allow an attacker in a Man-in-the-Middle position to modify network traffic sent on port 102/tcp to the affected devices.
How to fix
- siemens simatic_net_pc16 or later
- siemens simatic_step_716 or later
- siemens simatic_wincc16 or later
- siemens simatic_tim_1531_irc_firmware2.1 or later
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| siemens simatic_et_200sp_open_controller_cpu_1515sp_pc_firmware | No range specified | — |
| siemens simatic_et_200sp_open_controller_cpu_1515sp_pc2_firmware | No range specified | — |
| siemens simatic_s7-1200_cpu_1211c_firmware | v ≤ 4.0 | — |
| siemens simatic_s7-1200_cpu_1212c_firmware | v ≤ 4.0 | — |
| siemens simatic_s7-1200_cpu_1214c_firmware | v ≤ 4.0 | — |
| siemens simatic_s7-1200_cpu_1215c_firmware | v ≤ 4.0 | — |
| siemens simatic_s7-1200_cpu_1217c_firmware | v ≤ 4.0 | — |
| siemens simatic_s7-1500_cpu_1518_firmware | No range specified | — |
| siemens simatic_s7-1500_cpu_1511c_firmware | No range specified | — |
| siemens simatic_s7-1500_cpu_1512c_firmware | No range specified | — |
| siemens simatic_net_pc | v < 16 | 16 |
| siemens simatic_s7-1500 | No range specified | — |
| siemens simatic_s7-plcsim_advanced | No range specified | — |
| siemens simatic_step_7 | v < 16 | 16 |
| siemens simatic_wincc | v < 16 | 16 |
| siemens simatic_wincc_open_architecture | v ≤ 3.15, 3.16 | — |
| siemens simatic_wincc_runtime | No range specified | — |
| siemens simatic_cp_1626_firmware | No range specified | — |
| siemens simatic_tim_1531_irc_firmware | v < 2.1 | 2.1 |
| siemens simatic_hmi_panel_firmware | No range specified | — |
Check your version
Choose the product and enter the version you run to see whether it falls in the affected range.
Attack Surface Management