CVE-2019-10943

High

Description

A vulnerability has been identified in SIMATIC Drive Controller family (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V20.8), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V20.8), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.4.0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.8.1), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.8.1), SIMATIC S7-1500 Software Controller (All versions < V20.8), SIMATIC S7-1500 Software Controller (All versions >= V20.8), SIMATIC S7-PLCSIM Advanced (All versions < V3.0), SIMATIC S7-PLCSIM Advanced (All versions >= V3.0). An attacker with network access to port 102/tcp could potentially modify the user program on the PLC in a way that the running code is different from the source code which is stored on the device. An attacker must have network access to affected devices and must be able to perform changes to the user program. The vulnerability could impact the perceived integrity of the user program stored on the CPU. An engineer that tries to obtain the code of the user program running on the device, can receive different source code that is not actually running on the device.

SeverityHigh
CVSS7.5
Exploit probability—
ProductSiemens Simatic Et 200sp Open Controller Cpu 1515sp Pc Firmware
PublishedAug 13, 2019
First seenAug 13, 2019
Weakness typeCWE-353CWE-353

How to fix

Update
  • siemens simatic_et_200sp_open_controller_cpu_1515sp_pc2_firmware20.8 or later
  • siemens simatic_s7-1200_cpu_1211c_firmware4.4 or later
  • siemens simatic_s7-1200_cpu_1212c_firmware4.4 or later
  • siemens simatic_s7-1200_cpu_1214c_firmware4.4 or later
  • siemens simatic_s7-1200_cpu_1215c_firmware4.4 or later
  • siemens simatic_s7-1200_cpu_1217c_firmware4.4 or later
  • siemens simatic_s7-1500_cpu_1518_firmware2.8.1 or later
  • siemens simatic_s7-1500_cpu_1511c_firmware2.8.1 or later
  • siemens simatic_s7-1500_cpu_1512c_firmware2.8.1 or later
  • siemens simatic_s7-1500_software_controller20.8 or later
  • siemens simatic_s7_plcsim_advanced3.0 or later

Affected products

ProductAffected versionsFixed in
siemens simatic_et_200sp_open_controller_cpu_1515sp_pc_firmwareNo range specified—
siemens simatic_et_200sp_open_controller_cpu_1515sp_pc2_firmwarev < 20.820.8
siemens simatic_s7-1200_cpu_1211c_firmwarev < 4.44.4
siemens simatic_s7-1200_cpu_1212c_firmwarev < 4.44.4
siemens simatic_s7-1200_cpu_1214c_firmwarev < 4.44.4
siemens simatic_s7-1200_cpu_1215c_firmwarev < 4.44.4
siemens simatic_s7-1200_cpu_1217c_firmwarev < 4.44.4
siemens simatic_s7-1500_cpu_1518_firmwarev < 2.8.12.8.1
siemens simatic_s7-1500_cpu_1511c_firmwarev < 2.8.12.8.1
siemens simatic_s7-1500_cpu_1512c_firmwarev < 2.8.12.8.1
siemens simatic_s7-1500_software_controllerv < 20.820.8
siemens simatic_s7_plcsim_advancedv < 3.03.0

Check your version

Choose the product and enter the version you run to see whether it falls in the affected range.

In the Intelligence 360 plan

Attack Surface Management

See the assets tied to your domains, the technologies they run and known vulnerabilities in one list.