CVE-2019-18336

High

Description

A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V3.X.17), SIMATIC TDC CP51M1 (All versions < V1.1.8), SIMATIC TDC CPU555 (All versions < V1.1.1), SINUMERIK 840D sl (All versions < V4.8.6), SINUMERIK 840D sl (All versions < V4.94). Specially crafted packets sent to port 102/tcp (Profinet) could cause the affected device to go into defect mode. A restart is required in order to recover the system. Successful exploitation requires an attacker to have network access to port 102/tcp, with no authentication. No user interation is required. At the time of advisory publication no public exploitation of this security vulnerability was known.

SeverityHigh
CVSS7.5
Exploit probability—
ProductSiemens Simatic S7-300 Cpu Firmware
PublishedMar 10, 2020
First seenMar 10, 2020

How to fix

Update
  • siemens simatic_s7-300_cpu_firmware3.3.17 or later
  • siemens simatic_s7-300_cpu_312_ifm_firmware3.3.17 or later
  • siemens simatic_s7-300_cpu_313_firmware3.3.17 or later
  • siemens simatic_s7-300_cpu_314_firmware3.3.17 or later
  • siemens simatic_s7-300_cpu_314_ifm_firmware3.3.17 or later
  • siemens simatic_s7-300_cpu_315_firmware3.3.17 or later
  • siemens simatic_s7-300_cpu_315-2_dp_firmware3.3.17 or later
  • siemens simatic_s7-300_cpu_316-2_dp_firmware3.3.17 or later
  • siemens simatic_s7-300_cpu_318-2_firmware3.3.17 or later
  • siemens sinumerik_840d_sl4.8.6, 4.94 or later
  • siemens simatic_tdc_cp51m1_firmware1.1.8 or later
  • siemens simatic_tdc_cpu555_firmware1.1.1 or later

Affected products

ProductAffected versionsFixed in
siemens simatic_s7-300_cpu_firmwarev < 3.3.173.3.17
siemens simatic_s7-300_cpu_312_ifm_firmwarev < 3.3.173.3.17
siemens simatic_s7-300_cpu_313_firmwarev < 3.3.173.3.17
siemens simatic_s7-300_cpu_314_firmwarev < 3.3.173.3.17
siemens simatic_s7-300_cpu_314_ifm_firmwarev < 3.3.173.3.17
siemens simatic_s7-300_cpu_315_firmwarev < 3.3.173.3.17
siemens simatic_s7-300_cpu_315-2_dp_firmwarev < 3.3.173.3.17
siemens simatic_s7-300_cpu_316-2_dp_firmwarev < 3.3.173.3.17
siemens simatic_s7-300_cpu_318-2_firmwarev < 3.3.173.3.17
siemens sinumerik_840d_slv < 4.8.6, v < 4.944.8.6, 4.94
siemens simatic_tdc_cp51m1_firmwarev < 1.1.81.1.8
siemens simatic_tdc_cpu555_firmwarev < 1.1.11.1.1

Check your version

Choose the product and enter the version you run to see whether it falls in the affected range.

In the Intelligence 360 plan

Attack Surface Management

See the assets tied to your domains, the technologies they run and known vulnerabilities in one list.