CVE-2019-6577
Description
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The integrated web server could allow Cross-Site Scripting (XSS) attacks if an attacker is able to modify particular parts of the device configuration via SNMP. The security vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires system privileges and user interaction. An attacker could use the vulnerability to compromise confidentiality and the integrity of the affected system. At the stage of publishing this security advisory no public exploitation is known.
How to fix
- siemens simatic_hmi_comfort_panels_firmware15.1 or later
- siemens simatic_hmi_comfort_outdoor_panels_firmware15.1 or later
- siemens simatic_hmi_ktp_mobile_panels_ktp400f_firmware15.1 or later
- siemens simatic_hmi_ktp_mobile_panels_ktp700_firmware15.1 or later
- siemens simatic_hmi_ktp_mobile_panels_ktp700f_firmware15.1 or later
- siemens simatic_hmi_ktp_mobile_panels_ktp900_firmware15.1 or later
- siemens simatic_hmi_ktp_mobile_panels_ktp900f_firmware15.1 or later
- siemens simatic_wincc_\(tia_portal\)15.1 or later
- siemens simatic_wincc_runtime15.1 or later
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| siemens simatic_hmi_comfort_panels_firmware | v < 15.1 | 15.1 |
| siemens simatic_hmi_comfort_outdoor_panels_firmware | v < 15.1 | 15.1 |
| siemens simatic_hmi_ktp_mobile_panels_ktp400f_firmware | v < 15.1 | 15.1 |
| siemens simatic_hmi_ktp_mobile_panels_ktp700_firmware | v < 15.1 | 15.1 |
| siemens simatic_hmi_ktp_mobile_panels_ktp700f_firmware | v < 15.1 | 15.1 |
| siemens simatic_hmi_ktp_mobile_panels_ktp900_firmware | v < 15.1 | 15.1 |
| siemens simatic_hmi_ktp_mobile_panels_ktp900f_firmware | v < 15.1 | 15.1 |
| siemens simatic_wincc_\(tia_portal\) | v < 15.1 | 15.1 |
| siemens simatic_wincc_runtime | v < 15.1 | 15.1 |
| siemens simatic_hmi_tp_firmware | No range specified | — |
| siemens simatic_hmi_mp_firmware | No range specified | — |
| siemens simatic_hmi_op_firmware | No range specified | — |
Check your version
Choose the product and enter the version you run to see whether it falls in the affected range.
Attack Surface Management