CVE-2019-6577

Medium

Description

A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The integrated web server could allow Cross-Site Scripting (XSS) attacks if an attacker is able to modify particular parts of the device configuration via SNMP. The security vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires system privileges and user interaction. An attacker could use the vulnerability to compromise confidentiality and the integrity of the affected system. At the stage of publishing this security advisory no public exploitation is known.

SeverityMedium
CVSS5.4
Exploit probability—
ProductSiemens Simatic Hmi Comfort Panels Firmware
PublishedMay 14, 2019
First seenMay 14, 2019
Weakness typeCWE-80CWE-80

How to fix

Update
  • siemens simatic_hmi_comfort_panels_firmware15.1 or later
  • siemens simatic_hmi_comfort_outdoor_panels_firmware15.1 or later
  • siemens simatic_hmi_ktp_mobile_panels_ktp400f_firmware15.1 or later
  • siemens simatic_hmi_ktp_mobile_panels_ktp700_firmware15.1 or later
  • siemens simatic_hmi_ktp_mobile_panels_ktp700f_firmware15.1 or later
  • siemens simatic_hmi_ktp_mobile_panels_ktp900_firmware15.1 or later
  • siemens simatic_hmi_ktp_mobile_panels_ktp900f_firmware15.1 or later
  • siemens simatic_wincc_\(tia_portal\)15.1 or later
  • siemens simatic_wincc_runtime15.1 or later

Affected products

ProductAffected versionsFixed in
siemens simatic_hmi_comfort_panels_firmwarev < 15.115.1
siemens simatic_hmi_comfort_outdoor_panels_firmwarev < 15.115.1
siemens simatic_hmi_ktp_mobile_panels_ktp400f_firmwarev < 15.115.1
siemens simatic_hmi_ktp_mobile_panels_ktp700_firmwarev < 15.115.1
siemens simatic_hmi_ktp_mobile_panels_ktp700f_firmwarev < 15.115.1
siemens simatic_hmi_ktp_mobile_panels_ktp900_firmwarev < 15.115.1
siemens simatic_hmi_ktp_mobile_panels_ktp900f_firmwarev < 15.115.1
siemens simatic_wincc_\(tia_portal\)v < 15.115.1
siemens simatic_wincc_runtimev < 15.115.1
siemens simatic_hmi_tp_firmwareNo range specified—
siemens simatic_hmi_mp_firmwareNo range specified—
siemens simatic_hmi_op_firmwareNo range specified—

Check your version

Choose the product and enter the version you run to see whether it falls in the affected range.

In the Intelligence 360 plan

Attack Surface Management

See the assets tied to your domains, the technologies they run and known vulnerabilities in one list.