CVE-2021-45034
Description
A vulnerability has been identified in CP-8000 MASTER MODULE WITH I/O -25/+70°C (All versions < V16.20), CP-8000 MASTER MODULE WITH I/O -40/+70°C (All versions < V16.20), CP-8021 MASTER MODULE (All versions < V16.20), CP-8022 MASTER MODULE WITH GPRS (All versions < V16.20). The web server of the affected system allows access to logfiles and diagnostic data generated by a privileged user. An unauthenticated attacker could access the files by knowing the corresponding download links.
How to fix
- siemens cp-8000_master_module_with_i\/o_-25\/\+70_firmware16.20 or later
- siemens cp-8000_master_module_with_i\/o_-40\/\+70_firmware16.20 or later
- siemens cp-8021_master_module_firmware16.20 or later
- siemens cp-8022_master_module_with_gprs_firmware16.20 or later
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| siemens cp-8000_master_module_with_i\/o_-25\/\+70_firmware | v < 16.20 | 16.20 |
| siemens cp-8000_master_module_with_i\/o_-40\/\+70_firmware | v < 16.20 | 16.20 |
| siemens cp-8021_master_module_firmware | v < 16.20 | 16.20 |
| siemens cp-8022_master_module_with_gprs_firmware | v < 16.20 | 16.20 |
Check your version
Choose the product and enter the version you run to see whether it falls in the affected range.
Attack Surface Management
See the assets tied to your domains, the technologies they run and known vulnerabilities in one list.