CVE-2022-2502
Description
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.
How to fix
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| hitachienergy rtu500_firmware | 13.3.1, 13.3.2, 13.3.3, 13.4.1 | — |
Check your version
Choose the product and enter the version you run to see whether it falls in the affected range.
Attack Surface Management
See the assets tied to your domains, the technologies they run and known vulnerabilities in one list.