CVE-2022-28613
Description
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.
How to fix
- abb rtu500_firmware12.2.12.0 or later
- hitachienergy rtu500_firmware12.0.14.0, 12.4.12.0, 12.6.8.0, 12.7.4.0, 13.2.5.0 or later
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| abb rtu500_firmware | 12.2.1.0 ≤ v < 12.2.12.0 | 12.2.12.0 |
| hitachienergy rtu500_firmware | 12.0.1.0 ≤ v < 12.0.14.0, 12.4.1.0 ≤ v < 12.4.12.0, 12.6.1.0 ≤ v < 12.6.8.0, 12.7.1.0 ≤ v < 12.7.4.0, 13.2.1.0 ≤ v < 13.2.5.0 | 12.0.14.0, 12.4.12.0, 12.6.8.0, 12.7.4.0, 13.2.5.0 |