CVE-2022-31204

High

Description

Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations (such as project/logic uploads and downloads). This password is set using the OMRON FINS command Program Area Protect and unset using the command Program Area Protect Clear, both of which are transmitted in cleartext.

SeverityHigh
CVSS7.5
Exploit probability—
ProductOmron Sysmac Cs1 Firmware
PublishedJul 26, 2022
First seenJul 26, 2022

How to fix

Update
  • omron sysmac_cs1_firmware4.1 or later
  • omron sysmac_cj2m_firmware2.1 or later
  • omron sysmac_cj2h_firmware1.5 or later
  • omron sysmac_cp1e_firmware1.30 or later
  • omron sysmac_cp1h_firmware1.30 or later
  • omron sysmac_cp1l_firmware1.10 or later
  • omron cx-programmer9.6 or later

Affected products

ProductAffected versionsFixed in
omron sysmac_cs1_firmwarev < 4.14.1
omron sysmac_cj2m_firmwarev < 2.12.1
omron sysmac_cj2h_firmwarev < 1.51.5
omron sysmac_cp1e_firmwarev < 1.301.30
omron sysmac_cp1h_firmwarev < 1.301.30
omron sysmac_cp1l_firmwarev < 1.101.10
omron cp1w-cif41_firmwareNo range specified—
omron cx-programmerv < 9.69.6