CVE-2022-38465

Critical

Description

A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SINUMERIK MC (All versions < V6.21), SINUMERIK ONE (All versions < V6.21). Affected products protect the built-in global private key in a way that cannot be considered sufficient any longer. The key is used for the legacy protection of confidential configuration data and the legacy PG/PC and HMI communication. This could allow attackers to discover the private key of a CPU product family by an offline attack against a single CPU of the family. Attackers could then use this knowledge to extract confidential configuration data from projects that are protected by that key or to perform attacks against legacy PG/PC and HMI communication.

SeverityCritical
CVSS9.3
Exploit probability15. percentile0.2%
ProductSiemens Simatic Et 200 Sp Open Controller Cpu 1515sp Pc2 Firmware
PublishedOct 11, 2022
First seenOct 11, 2022
Weakness typeCWE-522CWE-522

How to fix

Update
  • siemens simatic_et_200_sp_open_controller_cpu_1515sp_pc2_firmware21.9 or later
  • siemens simatic_drive_controller_cpu_1504d_tf_firmware2.9.2 or later
  • siemens simatic_drive_controller_cpu_1507d_tf_firmware2.9.2 or later
  • siemens simatic_s7-1200_cpu_12_1211c_firmware4.5.0 or later
  • siemens simatic_s7-1200_cpu_12_1212c_firmware4.5.0 or later
  • siemens simatic_s7-1200_cpu_12_1212fc_firmware4.5.0 or later
  • siemens simatic_s7-1200_cpu_12_1214fc_firmware4.5.0 or later
  • siemens simatic_s7-1200_cpu_12_1214c_firmware4.5.0 or later
  • siemens simatic_s7-1200_cpu_12_1215fc_firmware4.5.0 or later
  • siemens simatic_s7-1200_cpu_12_1215c_firmware4.5.0 or later
  • siemens simatic_s7-1200_cpu_12_1217c_firmware4.5.0 or later
  • siemens simatic_s7-1500_cpu_1510sp-1_firmware2.9.2 or later

Affected products

ProductAffected versionsFixed in
siemens simatic_et_200_sp_open_controller_cpu_1515sp_pc2_firmwarev < 21.921.9
siemens simatic_et_200_sp_open_controller_cpu_1515sp_pc_firmwareNo range specified—
siemens simatic_drive_controller_cpu_1504d_tf_firmwarev < 2.9.22.9.2
siemens simatic_drive_controller_cpu_1507d_tf_firmwarev < 2.9.22.9.2
siemens simatic_s7-1200_cpu_12_1211c_firmwarev < 4.5.04.5.0
siemens simatic_s7-1200_cpu_12_1212c_firmwarev < 4.5.04.5.0
siemens simatic_s7-1200_cpu_12_1212fc_firmwarev < 4.5.04.5.0
siemens simatic_s7-1200_cpu_12_1214fc_firmwarev < 4.5.04.5.0
siemens simatic_s7-1200_cpu_12_1214c_firmwarev < 4.5.04.5.0
siemens simatic_s7-1200_cpu_12_1215fc_firmwarev < 4.5.04.5.0
siemens simatic_s7-1200_cpu_12_1215c_firmwarev < 4.5.04.5.0
siemens simatic_s7-1200_cpu_12_1217c_firmwarev < 4.5.04.5.0
siemens simatic_s7-1500_cpu_1510sp-1_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1510sp_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1511-1_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_151511c-1_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_151511f-1_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1511t-1_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1511tf-1_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1512c-1_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1512sp-1_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1512spf-1_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1513-1_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1513f-1_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1513r-1_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_15prof-2_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_15pro-2_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1515-2_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1515f-2_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1515r-2_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1515t-2_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1516pro_f_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1516-3_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1516f-3_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1516t-3_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1516tf-3_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1517-3_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1517f-3_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1518-4_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1518f-4_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1518hf-4_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1518t-4_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_cpu_1518tf-4_firmwarev < 2.9.22.9.2
siemens simatic_s7-1500_software_controllerv < 21.921.9
siemens simatic_s7-plcsim_advanced_firmwarev < 4.04.0

Check your version

Choose the product and enter the version you run to see whether it falls in the affected range.

In the Intelligence 360 plan

Attack Surface Management

See the assets tied to your domains, the technologies they run and known vulnerabilities in one list.