CVE-2024-6242
Description
A vulnerability exists in Rockwell Automation affected products that allows a threat actor to bypass the Trusted® Slot feature in a ControlLogix® controller. If exploited on any affected module in a 1756 chassis, a threat actor could potentially execute CIP commands that modify user projects and/or device configuration on a Logix controller in the chassis.
How to fix
Sources list no fixed version or patch link for this vulnerability.
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| Rockwell Automation ControlLogix® 5580 (1756-L8z) | V28 | — |
| Rockwell Automation GuardLogix® 5580 (1756-L8zS) | V31 | — |
| Rockwell Automation 1756-EN4TR | V2 | — |
| Rockwell Automation 1756-EN2T | v5.007(unsigned)/v5.027(signed), 1756-EN2T/D: V10.006 | — |
| Rockwell Automation 1756-EN2F | v5.007(unsigned)/v5.027(signed), 1756-EN2F/C: V10.009 | — |
| Rockwell Automation 1756-EN2TR | v5.007(unsigned)/v5.027(signed), 1756-EN2TR/C: V10.007 | — |
| Rockwell Automation 1756-EN3TR | v5.007(unsigned)/v5.027(signed), 1756-EN3TR/B: V10.007 | — |
| Rockwell Automation 1756-EN2TP | 1756-EN2TP/A: V10.020 | — |
Check your version
Choose the product and enter the version you run to see whether it falls in the affected range.
Attack Surface Management