CVE-2025-40753

Medium

Description

A vulnerability has been identified in POWER METER SICAM Q100 (7KG9501-0AA01-0AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q100 (7KG9501-0AA01-2AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q100 (7KG9501-0AA31-0AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q100 (7KG9501-0AA31-2AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q200 family (All versions >= V2.70 < V2.80). Affected devices export the password for the SMTP account as plain text in the Configuration File. This could allow an authenticated local attacker to extract it and use the configured SMTP service for arbitrary purposes.

SeverityMedium
CVSS6.2
Exploit probability—
ProductPOWER METER SICAM Q100
PublishedAug 12, 2025
First seenAug 12, 2025
Weakness typeCWE-312CWE-312

How to fix

Update
  • Siemens POWER METER SICAM Q100V2.62 or later
  • Siemens POWER METER SICAM Q200 familyV2.80 or later

Affected products

ProductAffected versionsFixed in
Siemens POWER METER SICAM Q100V2.60 ≤ v < V2.62V2.62
Siemens POWER METER SICAM Q200 familyV2.70 ≤ v < V2.80V2.80