CVE-2026-3611
Description
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
How to fix
- honeywell iq4e_firmware3.30 or later
- honeywell iq412_firmware3.30 or later
- honeywell iq422_firmware3.30 or later
- honeywell iq4nc_firmware3.30 or later
- honeywell iq41x_firmware3.30 or later
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| honeywell iq4e_firmware | v < 3.30 | 3.30 |
| honeywell iq412_firmware | v < 3.30 | 3.30 |
| honeywell iq422_firmware | v < 3.30 | 3.30 |
| honeywell iq4nc_firmware | v < 3.30 | 3.30 |
| honeywell iq41x_firmware | v < 3.30 | 3.30 |
Check your version
Choose the product and enter the version you run to see whether it falls in the affected range.
Attack Surface Management
See the assets tied to your domains, the technologies they run and known vulnerabilities in one list.