CVE-2026-4769

Critical

Description

Certain devices in the WAGO System I/O Field series activate an internal diagnostic capability during the initial startup sequence. This functionality is not formally documented and becomes accessible without authentication for a brief period in the early boot phase. During this window, an unauthenticated remote attacker can gain access to the internal system processes, resulting in full system compromise.

SeverityCritical
CVSS9.8
Exploit probability—
ProductWago 0765-110x/0100-0000
PublishedJul 13, 2026
First seenJul 13, 2026
Weakness typeCWE-912CWE-912

How to fix

Update
  • WAGO 0765-110x/0100-00001.2.1.100 or later
  • WAGO 0765-120x/0100-00001.2.7.100 or later
  • WAGO 0765-150x/0100-00001.2.7.103 or later
  • WAGO 0765-2101/0100-00001.2.1.102 or later
  • WAGO 0765-2102/0100-00001.2.5.101 or later
  • WAGO 0765-410x/0100-00001.2.1.100 or later
  • WAGO 0765-420x/0100-00001.2.7.100 or later
  • WAGO 0765-450x/0100-00001.2.7.103 or later

Affected products

ProductAffected versionsFixed in
WAGO 0765-110x/0100-00001.0.0.0 ≤ v < 1.2.1.1001.2.1.100
WAGO 0765-120x/0100-00001.0.0.0 ≤ v < 1.2.7.1001.2.7.100
WAGO 0765-150x/0100-00001.0.0.0 ≤ v < 1.2.7.1031.2.7.103
WAGO 0765-2101/0100-00001.0.0.0 ≤ v < 1.2.1.1021.2.1.102
WAGO 0765-2102/0100-00001.0.0.0 ≤ v < 1.2.5.1011.2.5.101
WAGO 0765-410x/0100-00001.0.0.0 ≤ v < 1.2.1.1001.2.1.100
WAGO 0765-420x/0100-00001.0.0.0 ≤ v < 1.2.7.1001.2.7.100
WAGO 0765-450x/0100-00001.0.0.0 ≤ v < 1.2.7.1031.2.7.103