CVE-2026-59693
Description
A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862), Desigo PXC4 (All versions < V02.21.194.36-2715), Desigo PXC5.E003 (All versions < V02.21.194.36-2715), Desigo PXC5.E24 (All versions < V02.21.194.36-2715), Desigo PXC7 (All versions < V02.21.194.36-2715). The affected devices are vulnerable to a denial-of-service (DoS) vulnerability. An attacker can exploit this issue by sending a malformed BACnet packet, causing the device to stop responding to BACnet queries. Recovery requires a device reset or reboot to restore normal functionality.
How to fix
- Siemens Desigo DXR2V01.21.233.16-7862 or later
- Siemens Desigo PXC3V01.21.233.16-7862 or later
- Siemens Desigo PXC4V02.21.194.36-2715 or later
- Siemens Desigo PXC5.E003V02.21.194.36-2715 or later
- Siemens Desigo PXC5.E24V02.21.194.36-2715 or later
- Siemens Desigo PXC7V02.21.194.36-2715 or later
Affected products
| Product | Affected versions | Fixed in |
|---|---|---|
| Siemens Desigo DXR2 | v < V01.21.233.16-7862 | V01.21.233.16-7862 |
| Siemens Desigo PXC3 | v < V01.21.233.16-7862 | V01.21.233.16-7862 |
| Siemens Desigo PXC4 | v < V02.21.194.36-2715 | V02.21.194.36-2715 |
| Siemens Desigo PXC5.E003 | v < V02.21.194.36-2715 | V02.21.194.36-2715 |
| Siemens Desigo PXC5.E24 | v < V02.21.194.36-2715 | V02.21.194.36-2715 |
| Siemens Desigo PXC7 | v < V02.21.194.36-2715 | V02.21.194.36-2715 |
Check your version
Choose the product and enter the version you run to see whether it falls in the affected range.