CVE-2026-59693

Medium

Description

A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862), Desigo PXC4 (All versions < V02.21.194.36-2715), Desigo PXC5.E003 (All versions < V02.21.194.36-2715), Desigo PXC5.E24 (All versions < V02.21.194.36-2715), Desigo PXC7 (All versions < V02.21.194.36-2715). The affected devices are vulnerable to a denial-of-service (DoS) vulnerability. An attacker can exploit this issue by sending a malformed BACnet packet, causing the device to stop responding to BACnet queries. Recovery requires a device reset or reboot to restore normal functionality.

SeverityMedium
CVSS4.3
Exploit probability—
ProductDesigo DXR2
PublishedAug 11, 2026
First seenAug 11, 2026
Weakness typeCWE-754CWE-754

How to fix

Update
  • Siemens Desigo DXR2V01.21.233.16-7862 or later
  • Siemens Desigo PXC3V01.21.233.16-7862 or later
  • Siemens Desigo PXC4V02.21.194.36-2715 or later
  • Siemens Desigo PXC5.E003V02.21.194.36-2715 or later
  • Siemens Desigo PXC5.E24V02.21.194.36-2715 or later
  • Siemens Desigo PXC7V02.21.194.36-2715 or later

Affected products

ProductAffected versionsFixed in
Siemens Desigo DXR2v < V01.21.233.16-7862V01.21.233.16-7862
Siemens Desigo PXC3v < V01.21.233.16-7862V01.21.233.16-7862
Siemens Desigo PXC4v < V02.21.194.36-2715V02.21.194.36-2715
Siemens Desigo PXC5.E003v < V02.21.194.36-2715V02.21.194.36-2715
Siemens Desigo PXC5.E24v < V02.21.194.36-2715V02.21.194.36-2715
Siemens Desigo PXC7v < V02.21.194.36-2715V02.21.194.36-2715

Check your version

Choose the product and enter the version you run to see whether it falls in the affected range.

In the Intelligence 360 plan

Attack Surface Management

See the assets tied to your domains, the technologies they run and known vulnerabilities in one list.